24 WSA-XEE 122-402
M02S40N16-00
6.12 Water reset
Menu accessible only after having entered the password.
Access reserved only to specically trained personnel.
The parameter modication can cause irreversible damages.
It is possible to limit the absorbed electric power with an external signal 0-10 Vcc or 4-20mA.
The water reset correction aects the setpoint dened by the Climate curve TExt (actual setpoint).
The setpoint is shown at status S0011: ActualSptWR
Only if P0051: En WaterReset ≠ 0
Path: Main Menu / Unit parameters / Water reset
Step Display Action Menu/Variable Keys Notes
1 Press 3 sec.
2 Password Set Password
3 Press
4 Main menu Select Unit parameters
5 Unit parameters Select Water reset
6 Water reset Select Parameter
7Set
8 Conrm
9 Press 3 sec.
10 Select Local connections
Path: Main Menu / Unit parameters / Water reset
Parameters Short description Description
P0063 TypeWR Inlet signal type: 0=0-10V; 1=4-20mA
P0281: MaxCWRC Maximum correction to be applied to the setpoint
P0283: SWRMaxC Value of the WR control signal corresponding to the correction of the set COOL equal to the parameter P0281
P0285 SWRMinC Value of the WR control signal corresponding to the correction of the set COOL equal to 0