M02S40N16-00 WSA-XEE 122-402 29
7.4 Change unit state
Step Display Action Menu/Variable Keys Notes
1 Press
2 Main menu Select Cmd Local state
3 Set OFF - ECO - ON - Pump On *
4 Conrm
6 Exit
* Local state
ECO: recurrent pump ON-OFF; compressors keep water system at setpoint ECO
Pmp ON: pump ON, compressor OFF
7.5 Change the mode
Step Display Action Menu/Variable Keys Notes
1 Press
2 Main menu Select Cmd Local mode
3Set
Cool: water cooling
Heat: water heating (option)
4 Conrm
5 Exit
7.6 Modify setpoint
Step Display Action Menu/Variable Keys Notes
1 Press
2 Main menu Select Unit parameters
3 Unit parameters Conrm Set Point
4 Select Set Point
5 Set Set Point
6 Conrm
7 Exit
Parameters Short description Description
P0001 SetPoint Cool Setpoint Cool
P0002 SetPoint Heat Setpoint Heat Not used
P0003 2°SetPoint Cool 2° Setpoint Cool Enable by remote switch
P0004 2°SetPoint Heat 2° Setpoint Heat not used currently
P0005 SetPoint ECOCool Economic summer SetPoint
P0006 SetPoint ECOHeat Economic winter SetPoint Not used
P0007 SetPointRec Recovery Set Point