24 WSA-XEE 182-352 M02S40N16-03
6.11 Climatic TExt
Menu accessible only after having entered the password.
Access reserved only to specically trained personnel.
The parameter modication can cause irreversible damages.
The setpoint dened by the temperature curve is shown at status S0010: ActualSptTExt
Only if P0053: En Climatica ≠ 0
Path: Main Menu / Unit parameters / Climatica TExt
Example
P0612
P0610
P0613
-5
5
10 15
5
10
15
25
30
P0606
P0609
P0607
18 22 24 26 28 30 32 34
2
4
6
8
10
12
14
16
34
0
25 30
20
0
20
T ext. T ext.
setpoint
setpoint
Cooling
P0608
Heating
P0611
S0052
S0052
20
Step Display Action Menu/Variable Keys Notes
1 Press 3 sec.
2 Password Set Password
3 Press
4 Main menu Select Unit parameters
5 Unit parameters Select Climatic TExt
6 Climatic TExt (pwd) Select Parameter
7 Set
8 Conrm
9 Press 3 sec.
10 Select Local connections
Path: Main Menu / Unit parameters / Climatica TExt
Parameters Short description Description
P0265: CSptLow setpoint temperature value when the air temperature value is AirAtSptLowC
P0266: AirAtSptLowC external air temperature value where the calculated setpoint takes on the value given by SptLowC
P0267: CSptHigh setpoint temperature value when the air temperature value is AirAtSptHigC
P0268: AirAtSptHigC external air temperature value where the calculated setpoint takes on the value given by SptHigC