IGL-RA15 2.0.0 Global Guide
7
2.3 LEDs color change
Each LED color is adjusted independently of controller output settings. If controller output 1 is set as “Common
Shutdown” it doesn’t mean red LED1 color for IGL-RA15. The LEDs color can by adjust by following steps:
Switch to programming mode (Hold the Horn reset and Lamp test when unit is powering on)
Status led is yellow
Press Horn reset to change the LED1 color (green, yellow, red)
Press Lamp test to switch to the next LED color adjusting
Continue to adjust all LEDs color
After LED15 color adjusting press three times Lamp test
Note: Signal LEDs are all adjusted to RED colors from production.
2.4 Horn timeout setting
The horn output is activated if any of red or yellow LED is on. Output is on until pressing Horn reset or horn
timeout counts down. The timeout can by set by following steps:
Switch to programming mode (Hold the Horn reset and Lamp test when unit is powering on)
Status led is yellow
Press Lamp test fifteen times
Set the horn timeout by pressing Horn reset.
The number of green luminous LEDs means timeout in 10s.
Any for disabling horn output, 1 for 10s timeout, 2 for 10s timeout, 15 for disabling horn timeout.
Press Lamp test two times
Note: Note: If there is no operator action during address setting, color adjusting or timeout timeout setting, the
unit returns to normal operation without changes saving.
2.5 Signal LEDs
The signals LEDs are handled like binary outputs. It means all what can be configured to binary outputs can be
also configured to the LEDs of iGL-RA15.
The LED lights, if configured logical output is active on the controller
The green LED is dark, if configured logical output is not active on the controller
The yellow or red LED is dark, if configured logical output is not active on the controller and horn reset was
pressed.
The yellow or red LED blinks, if configured logical output is not active on the controller and horn reset was
still not pressed.