13
TABLE for medium current values of 2,5 Amps
C/K
C = First bank power expressed in kvar (400V)
2,5 5 6 10 12,5 20 25 40 50
T.A. K
30/5 6 0.3 0.5 0.5 - - - - - -
50/5 10 0.3 0.3 0.4 0.5 - - - -
60/5 12 0.3 0.3 0.4 0.5 0.5 - - - -
80/5 16 0.2 0.3 0.3 0.5 0.5 0.5 - - -
100/5 20 0.2 0.3 0.3 0.3 0.4 0.5 0.5 - -
150/5 30 0.2 0.2 0.3 0.3 0.3 0.5 0.5 0.5 -
200/5 40 0.2 0.2 0.2 0.3 0.3 0.3 0.4 0.5 0.5
250/5 50 0.1 0.2 0.2 0.3 0.3 0.3 0.3 0.5 0.5
300/5 60 0.1 0.2 0.2 0.2 0.3 0.3 0.3 0.4 0.5
400/5 80 0.1 0.2 0.2 0.2 0.2 0.3 0.3 0.3 0.4
500/5 100 0.1 0.1 0.2 0.2 0.2 0.3 0.3 0.3 0.3
600/5 120 0.1 0.1 0.1 0.2 0.2 0.2 0.3 0.3 0.3
800/5 160 0.1 0.1 0.1 0.2 0.2 0.2 0.2 0.3 0.3
1000/5 200 0.1 0.1 0.1 0.1 0.2 0.2 0.2 0.3 0.3
1200/5 240 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.2 0.3
1500/5 300 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.2 0.2
2000/5 400 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.2
2500/5 500 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2
3000/5 600 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2
4000/5 800 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.2
5000/5 1000 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
When the CT secondary current signal is lower than 2 amps, the C/K value should be increased by 0,1
When using the regulator on 220/230 Vac networks the C/K values should be doubled.
“-” means installation of C.T. with primary value too small.
PF setting
After setting the C/K value, press the
Select
button again for 4 secs to indicate the selected PF required. At
the same the red led
PF
will illuminate. To release the
Select
button and use the
+
or
_
buttons to
change the selection. A PF of 0.95 is recommended.
Example: setted C/K = "0.3" setted PF = "0.97"
The regulator will switch bank to achieve a PF value within 0.94 and 1.00 (0.97 ± 0.03)
The “-” led near the two numbers display is illuminate if the P.F. value is more than 1.00.
6.1 SAVING the SET VALUES
By pressing the
Prog.
button the C/K and P.F. values which have been selected will be saved and the Regulator
works in AUTOMATIC condition.