© 2000 CONTRIVE • B1401.EN 0211 4 www.contrive.it
WARNINGS
CONFIGURATION
UNIT IN CONFIGURATION MODE THROUGH
COMMUNICATION LINK.
LOCKOUTS
FLAME LOSS
FLAME QUENCHING DURING NORMAL
BURNER OPERATION.
COMMUNICATION TIMEOUT
MISSING COMMANDS FROM REMOTE
SUPERVISOR.
RESETABLE FAILURES
IGNITION DEVICE FAILURE
IGNITION DEVICE UNPLUGGED, DEFECTIVE OR
NOT WORKING PROPERLY.
MISSING GROUND JOINT | SOFT JUMP
POOR SPARK RETURN PATH (I.E.: BAD
GROUND CONNECTION TO BURNERS HEAD).
GAS VALVE FAILURE
GAS VALVE UNPLUGGED, DEFECTIVE OR NOT
WORKING PROPERLY.
STRONG EMI | CONFIG ERROR
ELECTRO MAGNETIC INTERFERENCE ABOVE
ADMISSIBLE LIMIT, CONFIGURATION ERROR.
OUTPUT RELAYS FAILURE
SHORT CIRCUIT ON OUTPUT RELAYS CONTACT
SAFETY RELAY WILL DISCONNECT LOADS.
TIMEBASE FAILURE
MISMATCH BETWEEN 1
ST
AND 2
ND
TIMEBASE
GENERATORS.
SUPERVISOR ILLEGAL COMMAND
SUPERVISOR SENT AN ILLEGAL COMMAND
(i.e.: RESET WHILE SYSTEM IS RUNNING).
SYSTEM WATCHDOG
MICROPROCESSOR ISN’T OPERATING
PROPERLY.
NON RESETABLE FAILURES
MASTER SAFETY RELAY FAILURE
SHORT CIRCUIT ON SAFETY RELAY CONTACT.
OUTPUT RELAYS WILL DISCONNECT LOADS.