© 2000 CONTRIVE • B1401.EN 0211 7 www.contrive.it
PARAMETERS
BEHAVIOUR AT POWER ON – LOCKOUT
Q101 START-UP MODE AUTOSTART A
STANDBY S
BEHAVIOUR DURING PREPURGE
Q305 PREPURGE TIME 1” … 001
DEFAULT 1” … 250” 250
BEHAVIOUR DURING IGNITION
Q401 PRE-IGNITION TIME 0,5”
Q402 STARTUP SAFETY TIME 2” … 02
DEFAULT 3” … 25” 25
BEHAVIOUR DURING OPERATION
Q507 OPERATING SAFETY TIME 1” … 01
DEFAULT 1” … 12” 12
Q508 ALLOWED POSTCOMBUSTION TIME < 20”
Q509 AUTO-SHUTOFF TIME 00:05 … 01
20:50 … FA
Q510 AUTO-SHUTOFF MODE OFF –
MANUAL M
AUTOMATIC A
Q512 FLAME LOSS LOCKOUT L
RECYCLE C
RESPARK K
BEHAVIOUR DURING POSTPURGE
Q602 POSTPURGE TIME 1” … 001
DEFAULT 1” … 250” 250
COMMUNICATION SETTINGS
Q701 ZONE (SEGMENT) 00 …
… ZZ
Q702 UNIT (NODE) 00 …
… ZZ
Q703 BAUD RATE 4800
9600
19200
38400
Q704 TIMEOUT OFF
00’ 04”…
… 16’ 40”
LOCKOUT DUE TO COMMUNICATION TIMEOUT CAN OCCUR DURING
NORMAL CYCLE, WHEN COMMUNICATION TIMEOUT IS ENABLED
GENERAL SETTINGS
Q801 BURNER TYPE GAS G
OIL O
F809 DEVICE NOTES
F810 DEVICE PASSWORD
HARDWARE
Q001 POWER SUPPLY VOLTAGE 230 Vac 230
115 Vac 115
Q002 ENCLOSURE LIGHT ALUMINIUM N
STANDARD ALUMINIUM A
LOW PROFILE ALUMINIUM B
POLYCARBONATE P
CONFIGURATION
The device is configurable using the free software tool
QPro thru the communication line (terminals 4 and 5, by
means of TraxInterface
3
or TraxGateway) or from the
expansion socket (by means of specific adapter).
The unit must be in manual shutdown to enter confi-
guration environment: display shows an horizontal dash
while linked. Some parameters are password protected.
and can be modified by authorized users or by factory.