7
6.1 Troubleshooting (continued)
Please use caution when troubleshooting or repairing all electrical components. Be certain that
all power is disconnected from the COOL-SPACE
®
unit before the cooling pads are removed to
Water System
The water distribution system consists of two (2) assemblies:
o The Water Inlet Assembly
Brass bulkhead fitting
Float valve assembly
o The Hose and Valve Assembly
Spray Bar Assembly
Valve Assembly
Connection Hose
Floor at side of COOL-SPACE
®
unit is wet
Water inlet hose is loose at
supply hose or inlet hose is
loose at bulkhead fitting.
Tighten connections and/or
replace hose washers.
COOL-SPACE
®
unit overflows
from reservoir
Float valve is loose at bulkhead
fitting.
Water pressure is too high to
allow float valve to shutoff
Tighten connections and/or
replace hose washers. Reduce
water pressure by adding an
inline reducer.
Water spitting from the unit or
dripping from pads.
Flow of water too strong
Cracked Hose & Valve
Assembly.
Hose connection loose
Drip retainer on spray bar
Ensure pads were installed
Reduce flow
Replace Hose & Valve
Assembly.
Tighten hose
Adjust
Reinstall correctly
Water leaking from drain valve. For worn washer, worn stem.
Make sure drain valve is closed
Replace washer.
Replace drain valve.
Water leaking from water flow
Washer worn. Stem worn.
Jam nut or lock nut loose.
Replace water flow control
Too many dry streaks in the
pads.
Holes in spray bar blocked.
Adjust water flow.
Remove spray bar. Remove
plug and clean tube and holes.
Open water flow control valve.