© Corroventa Avfuktning AB
panel gives a warning
that the dehumidifier's
heat protection has
tripped.
machine has been
insufficient, which has
caused the temperature to
rise.
Check the filter and, if necessary, replace
it. The dehumidifier restarts auto-
matically when its internal temperature
has dropped.
If the fault persists after the above
action:
Check that the wet air duct is
unobstructed, that the wet air hose is
not pinched or sharply bent and that
nothing blocks its outlet on the outside
of the crawl space.
If the above does not restore operation,
check that the rotor in the dehumidifier
still rotates. Follow the instructions
under Service and maintenance in this
manual.
panel gives a warning
that the humidity in the
crawl space is too high.
The humidity in the crawl
space exceeds the set alarm
level.
Before further action, check that the
alarm level set in the system is relevant,
that the humidity now found in the crawl
space is a problem.
Check that the air leaving the wet air
hose outlet by the foundation wall is
warm and humid, see instructions under
Service and maintenance in this manual.
Check that the wet air hose is correctly
installed and has not come loose from
the dehumidifier.
Check that the rotor in the dehumidifier
still rotates. Follow the instructions
under Service and maintenance in this
manual.
Check the dry air distribution in the crawl
space, that the dry air is still freely
distributed via all nozzles in the entire
space according to the installation
description. If, for example, one of the
pipe's end plates has fallen off, the
necessary air distribution is not achieved.