21
E 121 - DTU 614 C2 Eng. 04.07.01
We reserve the right to make changes without notice
COSTER
26. COMPLEMENTARY FUNCTIONS
26.1 Password
Password selection and enabling. The command disables the use of keys + and –, so that data
cannot be modified. Enter the number (1900... 1999) using the + and – keys.
To delete password press + and – simultaneously until the dashes reappear.
If the + or – key is pressed when the password is enabled, the display will show a request to enter the
password. The + and – keys can only be used after entering the proper password. If no key is
pressed in the next 15 minutes, the password will be automatically re-enabled.
26.2 Site name
Site name as it appears on the first display page.
Each dash can be replaced with a letter (A...Z) or a number (0...9), using the + and – keys. The
key is used to position the cursor.
26.
3 Display of values and operating data
The controller displays all values measured by the detectors as well as all data that help understand
the system’s operating status:
• Actual room temperature – Rt (if B3 is connected) or flow temperature – Ft
(if only B1 is connected).
• Actual humidity
(if B6 is connected)
• Calculated flow temperature
based on Heating setting (if B3 and B1 are connected).
• Calculated flow temperature
based on Cooling setting (if B3 and B1 are connected).
• Actual temperature
measured by detector B1 (only if B3 and B1 are connected).
• Actual outside temperature
(
only if B2 is connected).
• Preheating desired and actual
temperature, only if B4 is connected and
• Dew point
desired and actual
temperature, only if B4 is connected and
• Setting of
desired
battery frostprotection temperature and
actual
value, only if B7 is connected
Output Y load value: Preheat. or Heat. or Ht.P.Hea. or Cool. or Frostprotection
Output Ys load value: DampTemp. or Recuper. or Dehumid.. or Humid.
Output Mu load value: Humidification
Battery frostprotection function load value
26.
4 Data recording
Every hour and with every mode change the controller stores a set of data indicating operating
status:
– Current date and time, type of recording (new hour or mode change)
– Current mode: On or Off; current season: Winter or Summer.
– Controller’s desired and calculated values
– Values measured by the detectors connected
– Outputs Y and Ys load value.
The controller is able to store 32 complete recordings, and the latest recording causes the oldest to
be deleted. If the display is not on page 1, the controller will perform the new hour recordings, but not
the mode change recordings, as it assumes that changes are being made on adjustment data.
Recordings can only be viewed from the Telemanagement computer.
M3.11
Password cho i ce
----
M3.12
Site Name
----------
Password
----
M0.1
Site------------
Rt :20.0c H%:50%
M0.15
Calculated Flow
Hea t i ng T : 22 . 0c
M0.18
Ac t ua l Out s i de
Tempera t . : 2. 0c
M0.20
Y-HEATING:100%
Ys-DAMP.TEM:100%
M0.16
Calculated Flow
Coo l i ng T . : 35 . 0c
M0.17
Ac t ua l F l ow
Tempera t . : 20 . 0c
M0.19
Des.Prheat:15.0c
Ac t .Prhea t : 15 . 0c
Des .Dewpnt : 15 . 0c
Ac t .Dewpnt : 15 . 0c
Use de t ec tor B4
PREHEAT I NG
M3.3
Use de t ec tor B4
DEWPOINT
M0.14
Des . Fros tp: 7 . 0c
Ac t .Fros t p: 35 . 0c
M0.21
Mu -HUMI D I F . : 100%
FROSTPR . : 100%