Page18
DehumidifierCR300onlyneedsaminimumofmaintenance.
Allcomponentsareservicefree,whichmeansnolubrication
oradjustment.
Onlythreethingsshouldbecheckedduringnormaloperati-
on:
-airfiltersshouldbereplacedatleastevery3months*)
-therotationoftherotorshouldbecheckedoncea
month.
-thereg.-temperatureduringoperationshouldbechecked
onceamonth(reg.outlet30-60C,dependingoninletcond.)
*)Filterforprocessair:
useourstandardfiltercassette180x180x48mm.Foreasy
replacingdolikethis:
-unscrewthecoverontopofthedehumidifier,andpull
thefilterout.
Iftherotorrotatesduringoperation,andthereg.-tempera-
tureis145Cat25Cinlet-youcanbealmostsurethatthe
dehumidifierisoperatingatanoptimum.
Weneverthelessrecommendsomeperiodicverificationof
theentiredehumidifier,toseeifallinternalfunctions
areokandcheckingofgasketsandmovingpartsforwear
andtear.
Thiswillensurethatthecapacityisonitsmaximum,and
thuswon`twasteanyenergy.
11.MAINTENANCE.
Rotationoftherotorcanbecheckedthroughtheholein
thecabinetplatewhenthegreyrubberplugisremoved.
Therotorshouldthenturndownwards.