15SV130 SV150 Installation - English
TECHNICAL MAINTENANCE
DISCONNECT THE VENTILATOR FROM POWER MAINS PRIOR TO ANY MAINTENANCE OPERATIONS WITH THE UNIT.
WARNING
Maintenance of the ventilator means regular cleaning of the ventilator surfaces of dust and cleaning or replacement of the lters
VENTILATOR MAINTENANCE
1. Fan inspection (once per year).
sedalb rellepmi eht naelCtinu noitalitnev eht evomeR
Take off the ventilation unit and clean the fan blades. To
remove dust use a soft brush, cloth or a vacuum cleaner. Do
not use water, abrasive detergents, solvents, sharp objects.
Clean the impeller blades once a year.
2. Regenerator and lter maintenance (3-4 times per year).
Filter
Ceramic regenerator
Filter
• Remove the air ow rectier.
• Remove the lter upstream of the regenerator.
• Pull the specially designed cord to remove the regenerator from the air duct.
• Be careful while removing the regenerator to avoid its damage.
• Remove the lter downstream of the regenerator.
Clean the lters as they get soiled, but not less than once in three months.
• After 90 days of operation the ventilator generates a sound signal after which
it is necessary to switch off the ventilator and to replace or clean
the lters.
• Wash the lters and let them get dry. Install dry lters in the air duct.
• Vacuum cleaning is allowed.
• The lter rated service life is 3 years.
• For new lters contact the Seller
Some dust may accumulate on the regenerator block even in case of regular
maintenance of the lters.
• Clean the regenerator regularly to ensure its high heat recovery efciency.
• Vacuum clean the regenerator not less than once a year.
To reset the hour meter install the lters and the regenerator into the ventilator and then press and hold the button for 10 sec. until you hear
a long sound signal.