Alarm Control Panel Installer Manual
37
NO: Establishes that the wired zone is not automatically excludable (it
blocks the arming of the Area which it belongs to).
YES: Establishes that the wired zone can be automatically bypass
permanently until the Area is disarmed.
WITH RESTORE: Establishes that the wired zone is automatically
excludable but, if it is not ready, it is taken back by the system and can
generate an alarm during the arming in progress.
Each individual wired zone can be programmed to react in differentiated
acoustic mode.
SIR&BUZZER: Establishes that the zone generates alarms both on the
buzzers and on the siren outputs.
CHIME: The CHIME is equivalent to the BUZZER and SIREN option
but adds the CHIME parameter to the zone. The CHIME parameter
makes it possible to control the zone, with the system disarmed,
activating the Keypad buzzer. However, to activate the zone CHIME,
you need to enable the zones to be controlled through the CHIME
ZONES menu of User Menu.
SILENT: Establishes that the wired zone does not generate any type of
sound alarm.
BUZZER: Establishes that the zone generates sound alarms only on
Keypad buzzers.
SIREN: Establishes that the zone generates sound alarms only on
In the case of multiple alarms (alarm repetition), you can determine the
behavior of the zones that remain open at the end of the alarm cycle in
progress. For example, a zone has set the value 3 to the ALARM
REPETITION parameter, if it remains open at the end of the activated alarm
cycle, you can decide that the alarm is not recycled (alarm cycle is set to
NO), or that the alarm is recycled a maximum of 3 times (alarm cycle is set
to YES).
This function is valid only for INSTANT, DELAY1&2, PATH, and EXIT END
zones.
Each individual wired zone can be programmed to generate a limited
number of alarm cycles during the arming phase. The value can be set from
00 through 10 cycles. The value 00 establishes a limitless number of alarm
cycles during the arming of the system. When a wired zone reaches the
programmed number of alarm cycles, the alarm system is momentarily
placed in a state of exclusion until disarming. On disarming, the alarm cycle
count is reset to zero.
Each individual wired zone can be programmed to command a LINK type
output every time it is opened. The corresponding LINK output must be then
programmed in the OUTPUT menu according to actual need (status and
duration).
If the setting remains at 000, no output will be affected.
The setting takes effect only if the selected output (from 001 to xxx) will be
programmed as a LINK type. This function is very useful for technological