Alarm Control Panel Installer Manual
46
The choice of the output polarity determines the at rest status of the output
itself. In practice, the output can be placed in HIGH or LOW electrical
status (high status gets more security)
DIRECT
If you press to confirm the option, you will exit and the output will
immediately take on the selected polarity.
GENERIC Outputs
The GENERIC outputs are only used by TIMERS (up to 4 timers).
In practice, the outputs are activated following the time slots on the Timers and the activation duration can
be programmed as TOGGLE (000.00=TOGGLE) or PULSE (timed).
Table 1-19 Generic outputs programming
Set the activation time of the output (minutes/seconds).
Setting it to 000.00 makes it Toggle.
Set an eventual delay time before output starts (minutes/seconds).
This parameter is shown only if the delay is programmed in impulse mode.
SINGLE: During its impulse activation, a further command does not
restart the impulse time. In this case, the LINK can reactivate only
after the entire impulse duration has elapsed.
CONTINUOUS: During its impulse activation, when another
command is received, the impulse time restarts from the beginning
time.
In practice, TRIGGER auto-regenerates at each new impulse until it
comes to the end of the set time.
TIMER1/TIMER2/
TIMER3/TIMER4
Follows the setting of Timers (00 to 16).
The outputs can also be associated with a maximum of 4 (Start/Stop)
TIMERS which can limit the outputs operation to specific time periods
during the week.
Press and or directly press the value + to alter the timer
to be set. After making the selection, press to move to the next field,
and after setting the fourth timer, press to move to the Polar screen.
The choice of the output polarity determines the at rest status of the output
itself. In practice, the output can be placed in HIHG or LOW electrical
status (high status gets more security)
DIRECT