SiBE121135 Indoor Unit Control (RA Models)
Function and Control 95
1.15 Inverter POWERFUL Operation
Outline In order to exploit the cooling and heating capacity to full extent, operate the air conditioner by
increasing the indoor fan rotating speed and the compressor frequency.
Detail When the [POWERFUL] button is pressed, the fan speed and target temperature are converted
to the following states for 20 minutes.
A = 40 ~ 90 rpm (depending on the model)
Ex: POWERFUL operation in cooling
Note: For Floor Standing Type: FVXG Series
POWERFUL operation is only available in RADIANT 1 (RADIANT operation with heating), it is
not available in RADIANT 2 (RADIANT operation only).
1.16 Multi-Colored Indicator Lamp / TIMER Lamp
Features Wall Mounted Type: FTXG Series
Current operation mode is displayed in color of the lamp of the indoor unit. Operating status can
be monitored even in automatic operation in accordance with the actual operation mode.
The lamp color changes according to the operation.
∗ AUTO ........................................................Red / Blue
∗ DRY ..........................................................Green
∗ COOL........................................................Blue
∗ HEAT ........................................................Red
∗ FAN...........................................................White
∗ TIMER.......................................................Orange
Operation mode Fan speed Target temperature
COOL H tap + A rpm 18°C
DRY Dry rotating speed + A rpm Lowered by 2 ~ 2.5°C
HEAT / RADIANT 1 H tap + A rpm 30 ~ 32°C
FAN H tap + A rpm —
AUTO Same as cooling / heating in
POWERFUL operation
The target temperature is kept
unchanged.
(R13571)
Target temp.
Fan
A rpm
18ËšC
H tap
Set tap
20 minutes
It should be the lower limit of
cooling temperature.
It counts 20 minutes. also
in the remote controller.
POWERFUL
ON
POWERFUL
OFF
Ending condition: "or" in 1 to 3
1. After the lapse of 20 minutes.
2. Operation OFF
3. POWERFUL operation is OFF.
(R15294)
Multi-colored indicator lamp /
TIMER lamp

Table of Contents

Other manuals for Daikin 3MXS40K2V1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 3MXS40K2V1B and is the answer not in the manual?

Daikin 3MXS40K2V1B Specifications

General IconGeneral
Model3MXS40K2V1B
CategoryAir Conditioner
Cooling Capacity4.0 kW
Outdoor Unit Weight34 kg
Power Supply220-240V / 50Hz / 1Ph
RefrigerantR32

Related product manuals