Troubleshooting for Duct Concealed/Ceiling Cassette Type SiUS122226E
184 Part 6 Service Diagnosis
6.12 Mismatching of Indoor Unit and Outdoor Unit
Error Code UA
Error Decision
Conditions
Improper combination of indoor and outdoor units
Supposed
Causes
Defective indoor unit PCB
Indoor-outdoor unit transmission wiring error
Defective optional unit(s) wirings
Improper power supply wiring of indoor unit
Improper wiring of connecting wires between indoor/outdoor units
Troubleshooting
Connect the wirings correctly.
Replace the indoor unit PCB
(control PCB).
Normal
Connect the wirings correctly.
Check the power supply system
inside the indoor unit.
Could be incorrect wiring.
Check again.
YES
YES
NO
NO
Connect the indoor/outdoor
units correctly.
YES
YES
YES
YES
NO
NO
NO
Blink
(R24591)
Is the combination
of indoor/outdoor
units correct?
Do(es) the indoor
unit service monitor(s)
blink?
Are the wirings
between indoor unit and
outdoor unit correctly
connected?
Connect the wirings correctly.
NO
Is the optional
units power supply
connected from the
indoor unit terminal
block No.1 and
No.2?
Does the system conduct
normal operation?
Are the wirings
between indoor unit and
outdoor unit correctly
connected?
Turn off the power supply.
Then, turn on the power
supply to restart the system.
Continuously
ON or OFF
Is the voltage
between No.1 and
No.2 on the indoor
unit terminal block
208 - 230
VAC?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 4MXL36WVJU9 and is the answer not in the manual?

Daikin 4MXL36WVJU9 Specifications

General IconGeneral
Model Number4MXL36WVJU9
CategoryAir Conditioner
BrandDaikin
RefrigerantR-410A
Frequency (Hz)60
Number of Connectable Indoor UnitsUp to 4
Inverter TechnologyYes
Cooling Capacity (BTU/h)36000
Voltage (V)208-230
PhaseSingle
Wi-Fi CapableYes