4. Typical BACnet® Server Gateway Application
DCM014A51 Quick User Guide 5
4. Typical BACnet® Server Gateway Application
1. The iTM BACnet® Server Gateway (DCM014A51) software option provides communication between the
VRV system and the BMS. The operation and monitoring of the VRV system through BACnet®
communication uses the BACnet®/IP protocol.
2. Up to 128 indoor unit management points (indoor units groups) can be controlled and monitored
through the iTM BACnet® Server Gateway.
3. Up to 7 additional DIII-Net communication systems can be added with the optional iTM Plus Adaptors.
4. The iTM BACnet® Server Gateway support change of value (COV).
5. The iTM BACnet® Server Gateway can be registered as a foreign device.
6. The iTM BACnet® Server gateway has a built-in virtual BACnet® router that provides seamless control
logic integration between the iTM and BMS.
a. Every indoor unit group address will be visible as BACnet® device on the BACnet® Network.
b. Indoor unit name on the iTM will be synced as BACnet® device name.
c. Allows ease of programming and graphics replication.