EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged reversible air to
water heatpumps
4PW51588-1
Operation manual
12
Field settings table
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Value Date Value
0 User permission level
00 User permission level 3 2/3 1
1 Weather dependent set point
00 Low ambient temperature (Lo_A) –10 –20~5 1 °C
01 High ambient temperature (Hi_A) 15 10~20 1 °C
02 Set point at low ambient temperature (Lo_TI) 40 25~55 1 °C
03 Set point at high ambient temperature (Hi_TI) 25 25~55 1 °C
2 Not available
3 Auto restart
00 Status 0 (ON) 0/1
4 Not available
5 Not available
6 Not available
7 Not available
8 Not available
9 Cooling and heating set point ranges
00 Heating set point upper limit 55 37~55 1 °C
01 Heating set point lower limit 15 15~37 1 °C
02 Cooling set point upper limit 22 18~22 1 °C
03 Cooling set point lower limit 5 5~18 1 °C
04 Overshoot setting 2 1~4 1 °C
A Quiet mode
00 Quiet mode type 0 0/2
01 Parameter 01 3—
C Alarm output logic of EKRP1HB
00 Not applicable. Do not change the default value! 0
01 Output logic of the EKRP1HB remote alarm
input/output PCB
0 0/1
D Benefit kWh rate power supply
00 Not available
01 Unit connection to benefit kWh rate power supply 0 (OFF) 0/1/2
02 Not applicable. Do not change the default value! 0
E Unit information readout
00 Software version Read
only
——
01 EEPROM version Read
only
——
02 Unit model identification Read
only
——
03 Liquid refrigerant temperature Read
only
——°C
04 Inlet water temperature Read
only
——°C