  • K
    Kelli JensenAug 17, 2025
    What to do if my Daikin EWAQ016CAW Chiller displays a high pressure error (SENPH/S1PH)?
    • M
      Mary SimmonsAug 18, 2025
      If your Daikin Chiller is showing a high pressure error (SENPH/S1PH), make sure the circuit is free of air, water flow is possible by opening all valves, the water filter isn't blocked, and all refrigerant stop valves are open. If the issue persists, it is best to contact your local dealer.
  • F
    fhayesAug 20, 2025
    How to fix water circuit malfunction in Daikin Chiller?
    • M
      Mary JenkinsAug 20, 2025
      To resolve a water circuit malfunction in your Daikin Chiller, ensure water flow is possible by opening all valves in the circuit. Additionally, try forcing clean water through the unit.
  • C
    Cynthia WilliamsAug 22, 2025
    What should I do if my Daikin Chiller has a water system warning?
    • P
      Patricia McdonaldAug 22, 2025
      If your Daikin Chiller is showing a water system warning, start by checking the filter and ensuring all valves are open. If the problem continues, it is best to contact your local dealer.
  • D
    David AguilarAug 26, 2025
    How to correct reversed power supply phase malfunction on Daikin Chiller?
    • B
      bellrobertAug 26, 2025
      If your Daikin Chiller displays a 'Reversed power supply phase malfunction', you should correct the phase order.
  • T
    Tammy McleanAug 27, 2025
    What to do if Daikin EWAQ016CAW shows insufficient supply voltage?
    • K
      Kenneth MillerAug 27, 2025
      If your Daikin Chiller is showing an insufficient supply voltage error, first check the wiring connections. If the problem persists, it is best to contact your local dealer.
  • M
    Michael ThompsonAug 30, 2025
    What to do if two main remote controllers are connected to my Daikin EWAQ016CAW?
    • A
      Ashley CannonAug 30, 2025
      If your Daikin Chiller displays 'Two main remote controllers are connected', verify that the SS1 setting of one controller is set to MAIN and the other is set to SUB. Then, turn the power supply off and back on.
  • K
    Kevin RoySep 2, 2025
    What does 'Type connection problem' mean on my Daikin Chiller and how to solve it?
    • R
      Ronald LittleSep 2, 2025
      If your Daikin Chiller is showing a 'Type connection problem', wait until initialization between the outdoor module and the hydro module is completed (wait at least 12 minutes after power ON). If the problem persists, it is best to contact your local dealer.
  • C
    Cynthia RiceSep 4, 2025
    How to troubleshoot R410A expansion valve error (K11E/K12E) in Daikin EWAQ016CAW Chiller?
    • R
      Robert MaxwellSep 4, 2025
      To address an R410A expansion valve error (K11E/K12E) on your Daikin Chiller, begin by checking the wiring connections. If the issue continues, it is best to contact your local dealer.
  • L
    Lauren HuntSep 6, 2025
    How to troubleshoot R410A liquid thermistor error (R13T/R23T) in Daikin EWAQ016CAW Chiller?
    • E
      Erika MartinezSep 6, 2025
      To address an R410A liquid thermistor error (R13T/R23T) on your Daikin Chiller, begin by checking the wiring connections. If the issue continues, it is best to contact your local dealer.
  • G
    Gabriel Rivera DDSSep 9, 2025
    How to troubleshoot R410A suction thermistor error (R14T/R24T) in Daikin EWAQ016CAW?
    • D
      Donna WadeSep 9, 2025
      To address an R410A suction thermistor error (R14T/R24T) on your Daikin Chiller, begin by checking the wiring connections. If the issue continues, it is best to contact your local dealer.

Daikin EWAQ016CAW Specifications

General IconGeneral
BrandDaikin
ModelEWAQ016CAW
CategoryChiller
LanguageEnglish

Related product manuals