Operation manual
1
EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30041-1A
C
ONTENTS
P
age
Introduction ....................................................................................... 1
Technical specifications ............................................................................. 1
Electrical specifications ............................................................................. 2
Description ........................................................................................ 2
Function of the main components.............................................................. 3
Safety devices............................................................................................ 4
Internal wiring - Parts table........................................................................ 4
Before operation................................................................................ 5
Checks before initial start-up ..................................................................... 5
Water supply.............................................................................................. 5
General recommendations ........................................................................ 5
Operation 16~24Hp........................................................................... 5
Digital controller......................................................................................... 5
Working with the 16~24Hp units................................................................ 6
Advanced features of the digital controller................................................. 8
Operation 32~72Hp......................................................................... 12
Digital controller....................................................................................... 12
Working with the 32~72Hp units.............................................................. 12
Advanced features of the digital controller............................................... 14
Troubleshooting............................................................................... 19
Maintenance.................................................................................... 20
Important information regarding the refrigerant used .............................. 20
Maintenance activities ............................................................................. 20
Disposal requirements............................................................................. 20
I
NTRODUCTION
This operation manual concerns packaged water-cooled water
chillers of the Daikin EWWP-KA series. These units are provided for
indoor installation and used for cooling and/or heating applications.
The units can be combined with Daikin fan coil units or air handling
units for air conditioning purposes. They can also be used for
supplying water for process cooling.
This manual has been prepared to ensure adequate operation and
maintenance of the unit. It will tell you how to use the unit properly
and will provide help if problems occur. The unit is equipped with
safety devices, but they will not necessarily prevent all problems
caused by improper operation or inadequate maintenance.
In case of persisting problems contact your local dealer.
Technical specifications
(1)
EWWP045KAW1M ECB1MUW
EWWP055KAW1M ECB2MUW
EWWP065KAW1M ECB3MUW
Packaged water-cooled water chillers
Operation manual
READ THIS MANUAL ATTENTIVELY BEFORE STARTING
UP THE UNIT. DO NOT THROW THIS MANUAL AWAY.
KEEP IT IN YOUR FILES FOR FUTURE REFERENCE.
Read the chapter "User settings menu" on page 14 before
changing the parameters.
Before starting up the unit for the first time, make sure that
it has been properly installed. It is therefore necessary to
carefully read the installation manual supplied with the unit
and the recommendations listed in "Checks before initial
start-up" on page 5.
(1) Refer to the engineering data book for the complete list of specifications.
General
Hp 16 20 24 32 36 40 44 48 52 56 60 64 68 72
Nominal cooling
capacity
(a)
(kW)
43.0 56.0 65.0 86 99 112 121 130 142 155 168 177 186 195
Nominal input
(b)
(kW)
12.1 16.0 18.3 24.2 28.1 32.0 34.3 36.6 40.2 44.1 48.0 50.3 52.6 54.9
Dimensions HxWxD
(mm)
600 x 600 x 1200 1200 x 600 x 1200 1800 x 600 x 1200
Machine weight
(kg)
300 320 334 600 620 640 654 668 920 940 960 974 988 1002
Connections
•water inlet (inch)
2x FBSP 1.5" 2x 2x FBSP 1.5" 3x 2x FBSP 1.5"
•water outlet (inch)
2x FBSP 1.5" 2x 2x FBSP 1.5" 3x 2x FBSP 1.5"
Compressor
Type
hermetically sealed scroll
Qty x model
2x
JT212DA-YE
2x
JT300DA-YE
2x
JT335DA-YE
4x
JT212DA-YE
2x
JT212DA-YE
+ 2x
JT300DA-YE
4x
JT300DA-YE
2x
JT300DA-YE
+ 2x
JT335DA-YE
4x
JT335DA-YE
4x
JT212DA-YE
+ 2x
JT300DA-YE
2x
JT212DA-YE
+ 4x
JT300DA-YE
6x
JT300DA-YE
4x
JT300DA-YE
+ 2x
JT335DA-YE
2x
JT300DA-YE
+ 4x
JT335DA-YE
6x
JT335DA-YE
Speed
(rpm)
2900 2900 2900
Oil type FVC 68D FVC 68D FVC 68D
Oil charge volume
(l)
2x 2.7 4x 2.7 6x 2.7
Evaporator
Type
brased plate heat exchanger
Qty 12 3
Nominal water flow
(l/min)
123 161 186 247 284 321 347 373 407 444 482 507 533 559
Water flow range
(l/min)
62 -247 80 - 321 93 - 373 123 - 493 142 - 568 161 - 642 173 -694 186 - 745
204 - 814 222 - 889 241 -963 254-1015 267-1066 280-1118
Condenser
Type
brased plate heat exchanger
Qty 12 3
Nominal water flow
(l/min)
157 205 237 314 362 410 442 474 519 567 614 647 679 711
Water flow range
(l/min)
79 - 314 102 - 410 118 - 474 157 - 629 181 -724 205 - 819 221 - 883 237 - 948
260-1038 283-1133 307-1229 323-1293 339-1357 355-1422
(a) The nominal cooling capacity is based on:
-entering water temperature of 12°C
-chilled water temperature of 7°C
-condenser in/out water temperature of 30/35°C
(b) The nominal input includes total input of the unit: compressor, control circuit and water pumps.