ESIE15-13B Troubleshooting by Remote Controller
Service Diagnosis 123
4.3 Safety Devices
4.3.1 Outdoor Unit
4.3.2 Indoor Unit
Model
High pressure switch
Fuse
Open Close
RZQG71L 4.0 MPa +0/– 0.15 3.0 MPa ± 0.15 6.3A/250V (F1U), 3.15A/250V (F6U)
RZQG100L 6.3A/250V (F1U, F2U, F3U),
5A/250V (F6U)RZQG125L
RZQG140L
Model
Thermal protector
Fuse
Abnormal Reset (automatic)
FCQG
——
N.A.
FHQG 3.15A/250V (F1U)