4 Preparation
Installation and operation manual
5
FCAG35~140AVEB
Split system air conditioners
4P471224-1 – 2017.03
Outdoor units Cooling Heating
AZAS71~140 Outdoor
temperature
–15~46°CDB –14~21°CDB
–15~15.5°CWB
Indoor
temperature
20~37°CDB
14~28°CWB
10~27°CDB
Indoor humidity ≤80%
(a)
(a) To avoid condensation and water dripping out of the unit. If
the temperature or the humidity is beyond these conditions,
safety devices may be put in action and the air conditioner
may not operate.
3.2 System layout
a Indoor unit
b Outdoor unit
c User interface
d Suction air
e Discharge air
f Refrigerant piping + interconnection cable
g Drain pipe
h Earth wiring
i Suction grille and air filter
4 Preparation
4.1 Preparing installation site
4.1.1 Installation site requirements of the
indoor unit
INFORMATION
The sound pressure level is less than 70dBA.
CAUTION
Appliance not accessible to the general public, install it in a
secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for
installation in a commercial and light industrial
environment.
▪ Spacing. Mind the following requirements:
(mm)
≥1500
≥
2000
≥
4000
≥1500
A
B
C
ba dac
A Minimum distance to the wall (see below)
B Minimum and maximum distance to the floor (see below)
C 35~71 class:
≥214mm: In case of installation with standard panel
≥294mm: In case of installation with self-cleaning panel
≥263mm: In case of installation with fresh air intake kit
100~140 class:
≥256mm: In case of installation with standard panel
≥306mm: In case of installation with fresh air intake kit
≥316mm: In case of installation with self-cleaning panel
a Indoor unit
b Lighting (the figure shows ceiling-mounted lighting, but
recessed lighting is also allowed)
c Air fan
d Static volume (example: table)
▪ A: Minimum distance to the wall. Depends on the air flow
directions towards the wall.
a Air outlet and corners open
b Air outlet closed, corners open (optional blocking pad kit
required)
c Air outlet and corners closed (optional blocking pad kit
required)
▪ B: Minimum and maximum distance to the floor:
▪ Minimum: 2.5m to avoid accidental touching.
▪ Maximum: Depends on the air flow directions and the capacity
class. Also make sure the "Ceiling height" field setting
corresponds with the actual situation. See Field settings.
If air flow direction… Then B
FCAG35~71 FCAG100~140
All-round ≤3.5m ≤4.2m
4-way
(a)
≤4.0m ≤4.5m
3-way
(a)
≤3.5m ≤4.2m
(a) Optional blocking kit required
5 Installation
5.1 Mounting the indoor unit
5.1.1 Guidelines when installing the indoor unit
INFORMATION
Optional equipment. When installing optional equipment,
also read the installation manual of the optional equipment.
Depending on the field conditions, it might be easier to
install the optional equipment first.
▪ In case of installation with a fresh air intake kit. Install the
fresh air intake kit always before installing the unit.
▪ Decoration panel. Install the decoration panel always after
installing the unit.