4 About the units and options
Installer and user reference guide
10
FCAG35~140AVEB
Split system air conditioners
4P473927-1 – 2017.03
4.2.1 Identification label: Indoor unit
Location
4.3 About the indoor unit
Use the system in the following temperature and humidity ranges for
safe and effective operation.
For combination with R410A outdoor unit, refer to the following table:
Outdoor units Cooling Heating
RR71~125 Outdoor
temperature
–15~46°CDB —
Indoor
temperature
18~37°CDB
12~28°CWB
—
RQ71~125 Outdoor
temperature
–5~46°CDB –9~21°CDB
–10~15°CWB
Indoor
temperature
18~37°CDB
12~28°CWB
10~27°CDB
RXS35~60 Outdoor
temperature
–10~46°CDB –15~24°CDB
–16~18°CWB
Indoor
temperature
18~32°CDB 10~30°CDB
3MXS40~68
4MXS68~80
5MXS90
Outdoor
temperature
–10~46°CDB –15~24°CDB
–16~18°CWB
Indoor
temperature
18~32°CDB 10~30°CDB
RZQG71~140 Outdoor
temperature
–15~50°CDB –19~21°CDB
–20~15.5°CWB
Indoor
temperature
18~37°CDB
12~28°CWB
10~27°CDB
RZQSG71~140 Outdoor
temperature
–15~46°CDB –14~21°CDB
–15~15.5°CWB
Indoor
temperature
20~37°CDB
14~28°CWB
10~27°CDB
RZQ200~250 Outdoor
temperature
–5~46°CDB –14~21°CDB
–15~15°CWB
Indoor
temperature
20~37°CDB
14~28°CWB
10~27°CDB
AZQS71~125 Outdoor
temperature
–15~46°CDB –14~21°CDB
–15~15.5°CWB
Indoor
temperature
20~37°CDB
14~28°CWB
10~27°CDB
For combination with R32 outdoor unit, refer to the following table:
Outdoor units Cooling Heating
RXM35~60 Outdoor
temperature
–10~46°CDB –15~24°CDB
–16~18°CWB
Indoor
temperature
18~32°CDB 10~30°CDB
Outdoor units Cooling Heating
3MXM40~68
4MXM68~80
5MXM90
Outdoor
temperature
–10~46°CDB –15~24°CDB
–16~18°CWB
Indoor
temperature
18~32°CDB 10~30°CDB
RZAG71~140 Outdoor
temperature
–20~52°CDB –19.5~21°CDB
–20~15.5°CWB
Indoor
temperature
18~37°CDB
12~28°CWB
10~27°CDB
RZASG71~140 Outdoor
temperature
–15~46°CDB –14~21°CDB
–15~15.5°CWB
Indoor
temperature
20~37°CDB
14~28°CWB
10~27°CDB
AZAS71~140 Outdoor
temperature
–15~46°CDB –14~21°CDB
–15~15.5°CWB
Indoor
temperature
20~37°CDB
14~28°CWB
10~27°CDB
Indoor humidity ≤80%
(a)
(a) To avoid condensation and water dripping out of the unit. If
the temperature or the humidity is beyond these conditions,
safety devices may be put in action and the air conditioner
may not operate.
4.4 System layout
a Indoor unit
b Outdoor unit
c User interface
d Suction air
e Discharge air
f Refrigerant piping + interconnection cable
g Drain pipe
h Earth wiring
i Suction grille and air filter
4.5 Combining units and options
4.5.1 Possible options for the indoor unit
Make sure you have the following mandatory options:
▪ User interface: Wired or wireless
▪ Decoration panel: Standard or self-cleaning