1-14
R
S
T
N
COMP
L
N
COMP
L
N
Indoor Unit
Terminal Block
Interconnection Cable
Outdoor Unit
Terminal Block
Power Supply Cable
Model Indoor (FCRN) 100E 100E
Outdoor (RR) 90D 100D
Voltage range** Indoor (FCRN)
220-240V/1Ph/50Hz +
!
Outdoor (RR)
220-240V/1Ph/50Hz + !
Power supply cable size* (mm
2
)
Number of conductors
4.0
3
4.0
3
Interconnection cable size* (mm
2
)
Number of conductors
2.5
4
2.5
4
Recommended time delay fuse* (A) 25 30
Model Indoor (FCRN) 100E 125E
Outdoor (RR) 100D 125D
Voltage range** Indoor (FCRN)
220-240V/1Ph/50Hz + !
Outdoor (RR)
380-415V/3N~/50Hz + !
Power supply cable size* (mm
2
)
Number of conductors
2.5
5
4.0
5
Interconnection cable size* (mm
2
)
Number of conductors
1.5
4
1.5
4
Recommended time delay fuse* (A) 13 18
FCRN 100/125E - RR 100/125D (3 PH)
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.
1 IM-5CKE-0912(0)DAIKIN-EN.indd 141 IM-5CKE-0912(0)DAIKIN-EN.indd 14 9/28/12 2:04:18 PM9/28/12 2:04:18 PM