1-16
Model Indoor (FCQN) 100E 100E
Outdoor (RQ) 90D 100D
Voltage range** Indoor (FCQN)
220-240V/1Ph/50Hz +
!
Outdoor (RQ)
220-240V/1Ph/50Hz + !
Power supply cable size* (mm
2
)
Number of conductors
4.0
3
4.0
3
Interconnection cable size* (mm
2
)
Number of conductors
2.5
3&4
2.5
3&4
Recommended time delay fuse* (A) 25 30
A
4WV
OF
COMP
N
L
R
S
T
N
4WV
A
OF
L
N
COMP
Indoor Unit
Terminal Block
Interconnection Cable
Outdoor Unit
Terminal Block
Power Supply Cable
Outdoor Coil Sensor
FCQN 100/125E - RQ 100/125D (3 PH)
Model Indoor (FCQN) 100E 125E
Outdoor (RQ) 100D 125D
Voltage range** Indoor (FCQN)
220-240V/1Ph/50Hz + !
Outdoor (RQ)
380-415V/3N~/50Hz + !
Power supply cable size* (mm
2
)
Number of conductors
2.5
5
2.5
5
Interconnection cable size* (mm
2
)
Number of conductors
1.5
3&4
1.5
3&4
Recommended time delay fuse* (A) 13 18
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.