ESIE05-04 Disassembly and Maintenance
Part 5 – Disassembly and Maintenance 5–39
3
5
1
5
2 Removing the drain pump
1
Cut the clamp material.
2
Pull the drain hose out.
3
Remove the 3 screws
on the drain pump
mounting plate.
4
Remove the 2 mounting
screws on the drain
pump.
5
Displace the drain pump
sideward to remove it.
Q When removing the drain
pump, cut the following clamp
materials.
z Clamp material securing the
drain pump lead wire to the
drain pump mounting plate.
z Clamp material bundling the
drain pump lead wire and float
switch lead wire.
3 Removing the float switch
Q When removing the float
switch, cut the following clamp
materials.
z Clamp material securing the
drain pump lead wire to the
drain pump mounting plate.
z Clamp material bundling the
drain pump lead wire and
float switch lead wire.
1
Reverse the drain pump
mounting plate which
was removed according
to the procedure
described on the
preceding page.
2
Remove the 1 screw,
displace the float switch
sideward, then
dismount the float
switch.
Step
Procedure Points
Clamp materia
Drain pump