ESIE05-04 Disassembly and Maintenance
Part 5 – Disassembly and Maintenance 5–121
3
5
1
5
1.15.8 Drain Hose Piping to the Left
Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step Procedure Points
Q Removing the front grille in
accordance with "Removal
of Front Grille".
Q The drain pan and bottom
frame are designed as an
integral-type.
Q Insert the drain hose to the
hose plug securely as far as it
will go.
1 Pull out the drain hose
attached on the rear right
of the unit.
2 Pull out the drain plug
and drain socket
attached on the rear left
of the unit.
3 Piping of Drain Hose at
Left Side.
4 Insert the drain plug and
drain socket into the right
side of the unit with
hexagonal pin wrench.
Q Insert the drain plug and
socket securely as far as it will
go.