EasyManua.ls Logo

Daikin FFQ25B9V1B - Drain Water Level System Abnormality

Daikin FFQ25B9V1B
462 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SiBE121135 Troubleshooting for SA Indoor Unit - FCQG, FFQ, FHQ, FDBQ, FBQ Series
Service Diagnosis 285
6.2 Drain Water Level System Abnormality
Remote
Controller
Display
A3
Method of
Malfunction
Detection
The float switch detects error.
Malfunction
Decision
Conditions
When the water level reaches its upper limit and when the float switch turns OFF
Supposed
Causes
Defective drain pump
Improper drain piping work
Clogged drain piping
Defective float switch
Defective indoor unit PCB
Defective short circuit connector X15A on indoor unit PCB

Table of Contents

Other manuals for Daikin FFQ25B9V1B

Related product manuals