Field Settings SiBE121135
418 Trial Operation and Field Settings
Wireless Remote
Controller
(1) Remove the cover and take it off.
(2) Cut the address setting jumper.
5.2.3 Jumper and Switch Settings
<Floor Standing Type: FVXS Series>
<Floor / Ceiling Suspended Dual Type>
For the location of the jumper and the switch, refer to the following pages.
Wall Mounted Type: page 42, 45, 47, 50
Floor Standing Type: page 53, 56
Floor / Ceiling Suspended Dual Type: page 58
Duct Connected Type: page 60
ARC466 series ARC452 series
ARC433 series
Jumper
(R12037)
ADDRESS
EXIST
1
CUT
2
Jumper
ADDRESS
(R12065)
EXIST
CUT
1
2
Jumper
(R6573)
ADDRESS
EXIST
CUT
1
2
Jumper (on indoor
unit PCB)
Function When connected
(factory set)
When cut
JB Fan speed setting
when compressor
stops for thermostat
OFF. (effective only
at cooling operation)
Fan speed setting ;
Remote controller
setting
Fan speed setting; “0” (The fan
stops.)
JC Power failure
recovery function
Auto-restart The unit does not resume
operation after recovering from a
power failure. Timer settings are
cleared.
Switch (on indoor unit
PCB)
Function OFF (factory set) ON
SW2-4 Upward airflow limit
setting
Exposed or half
embedded
installation
Set the switch to ON position
when you install the indoor unit
embedded in the wall to avoid
condensation.
Switch (on indoor unit
PCB)
Function FLOOR (factory
set)
CEILING
SW2 Installation style
changeover
When installed as
the floor mounted
type
When installed as the ceiling
suspended type