1
Installation manual
FHB35FK7V1 FHYB35FK7V1 FHYB71FK7V1
FHB45FK7V1 FHYB45FK7V1 FHYB100FK7V1
FHB60FK7V1 FHYB60FK7V1 FHYB125FK7V1
Before installation ..................................................................... 1
Selecting installation site .......................................................... 2
Preparations before installation ............................................... 2
Indoor unit installation .............................................................. 3
Refrigerant piping work ............................................................ 3
Drain piping work ...................................................................... 4
Electric wiring work ................................................................... 4
Wiring example and how to set the remote controller ............. 5
Wiring example ......................................................................... 5
Installation of the decoration panel .......................................... 6
Test operation ........................................................................... 6
Wiring diagram ......................................................................... 7
page
Split System air conditioners
READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.
BEFORE INSTALLATION
Leave the unit inside its packaging until you reach the
installation site. Where unpacking is unavoidable, use a sling
of soft material or protective plates together with a rope when
lifting, this to avoid damage or scratches to the unit.
Refer to the installation manual of the outdoor unit for items
not described in this manual.
Precautions
Do not install or operate the unit in rooms mentioned below.
Places with mineral oil, or filled with oil vapour or spray like
in kitchens. (Plastic parts may deteriorate.)
Where corrosive gas like sulphurous gas exists. (Copper
tubing and brazed spots may corrode.)
Where volatile flammable gas like thinner or gasoline is used.
Where machines generating electromagnetic waves exist.
(Control system may malfunction.)
Where the air contains high levels of salt such as air near
the ocean and where voltage fluctuates a lot (e.g. in
factories). Also in vehicles or vessels.
When selecting the installation site, use the supplied paper
pattern for installation.
Washer for hanging
bracket
8 pcs.
for gas pipe for liquid pipe
Insulation for fitting
1 each
Screws for fixing the
paper pattern
for installation
6 pcs.
Drain hose
1 pc.
Metal clamp
1 pc.
Paper pattern for
installation
1 pc.
Accessories
Check if the following accessories are included with your unit.
Screws for
duct flanges
1 set
FH(Y)B35•45 8 pcs.
FH(Y)B60•71 12 pcs.
FHYB100•125 16 pcs.
Other: installation and operation manual
Screws for fixing panels are attached to the air inlet panel.
Optional accessories
Select an optional remote controller according to customer
request and install in an appropriate place.
Refer to catalogues and technical literature for selecting a
suitable remote controller.
When installing bottom suction: air inlet panel and canvas
connection for the air inlet panel.