13
Application Information
3) Cable Size
Cooling only
Model Unit
FF10/15CXV1 FF20CXV1 FHC20EXV1
R10/15CXV1 R20CXV1 R20CXV1
Power supply cable size
Number of wire
mm²
1.5
3
2.5
3
2.5
3
Interconnection cable size
Number of wire
mm²
1.5
3
2.5
3
2.5
3
Recommended fuse A 15 20 13
Model Unit
FHC25EXV1 FHC28EXV1 FHC40EXV1
R25CXV1 R28CXV1 R35DXV1
Power supply cable size
Number of wire
mm
2
2.5
3
4.0
3
4.0
3
Interconnection cable size
Number of wire
mm
2
2.5
3
2.5
3
2.5
4
Recommended fuse A 18 25 25
Model Unit
FHC40EXV1 FHC40EXV1 FHC50EXV1
R40DXV1 R40DXY1 R50DXY1
Power supply cable size
Number of wire
mm
2
4.0
3
2.5
5
2.5
5
Interconnection cable size
Number of wire
mm
2
2.5
4
1.5
4
1.5
4
Recommended fuse A 30 13 18
Heatpump
Model Unit
FFY10/15CXV1 FFY20CXV1 FHYC20EXV1
RY10/15CXV1 RY18/20CXV1 RY20CXV1
Power supply cable size
Number of wire
mm
2
1.5
3
2.5
3
2.5
3
Interconnection cable size
Number of wire
mm
2
1.5
3
2.5
5
2.5
5
Recommended fuse A 15 20 13
Model Unit
FHYC25EXV1 FHYC28EXV1 FHYC40EXV1
RY25CXV1 RY28CXV1 RY35DXV1
Power supply cable size
Number of wire
mm
2
2.5
3
4.0
3
4.0
3
Interconnection cable size
Number of wire
mm
2
2.5
5
2.5
5
2.5
3 & 4
Recommended fuse A 18 18 25
Model Unit
FHYC40EXV1 FHYC40EXV1 FHYC50EXV1
RY40DXV1 RY40DXY1 RY50DXY1
Power supply cable size
Number of wire
mm
2
4.0
3
2.5
5
2.5
5
Interconnection cable size
Number of wire
mm
2
2.5
3 & 4
1.5
3 & 4
1.5
3 & 4
Recommended fuse A 30 13 13
DAIKIN_FF_FHC.indb 13DAIKIN_FF_FHC.indb 13 9/27/2012 2:04:52 PM9/27/2012 2:04:52 PM