Si20-701_B Troubleshooting by Remote Controller
272
Note:
1. Radiation fin temperature detection value
Model Detection Reset
RZQ
RZQ100~140B8W1B
76°C 66°C
RZR71KUV1
RZQ71B9V3B
RZQS71·100B7V3B
RZQ71C7V1B
RZQS71·100C7V1B
87°C 77°C
RZQG71LV1B 85°C 75°C
RZR100~140KUV1
RZR100~140HUY1
RZR-KUV2S
RZR-HUY2S
RZQ100~140C7V1B
RZQS125·140C7V1B
88°C 78°C
RZQG100~140LV1B 89°C 79°C
Is the error
displayed again
when the unit starts
operation?
YES
Replace the
outdoor unit
inverter PCB.
Continue the
operation.
NO
A
YES
Check the resistance
value of the thermistor
according to the
Troubleshooting "P4".
Is it
normally?
NO
Go to
troubleshooting
"P4".
A
B