46
Capacity Tables
3D122963
3D122965
Model: FTV50A - RV50A
Cooling : 230V 50Hz
AFR 12.46
BF 0.147
Indoor Temperature Outdoor temperature [°C DB]
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14 20 5.41 3.75 1.26 5.16 3.63 1.39 4.91 3.51 1.51 4.81 3.47 1.55 4.67 3.39 1.64 4.42 3.28 1.75
16 22 5.65 3.69 1.27 5.40 3.57 1.39 5.15 3.46 1.52 5.06 3.42 1.57 4.91 3.35 1.64 4.67 3.25 1.76
18 25 5.90 3.85 1.28 5.65 3.75 1.41 5.40 3.64 1.52 5.31 3.60 1.57 5.15 3.54 1.65 4.91 3.44 1.77
19 27 6.01 4.05 1.28 5.77 3.94 1.41 5.52 3.85 1.52 5.42 3.80 1.57 5.28 3.75 1.65 5.03 3.66 1.78
22 30 6.38 3.90 1.29 6.13 3.81 1.42 5.88 3.72 1.54 5.79 3.69 1.59 5.64 3.63 1.66 5.40 3.55 1.79
Model: FTV60A - RV60A
Cooling : 230V 50Hz
AFR 19.54
BF 0.155
Indoor Temperature Outdoor temperature [°C DB]
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14 20 7.21 5.00 1.70 6.87 4.84 1.86 6.55 4.69 2.03 6.42 4.63 2.09 6.22 4.52 2.20 5.89 4.37 2.36
16 22 7.54 4.92 1.71 7.20 4.76 1.87 6.86 4.62 2.04 6.75 4.56 2.11 6.55 4.47 2.20 6.22 4.33 2.37
18 25 7.86 5.14 1.72 7.54 5.00 1.89 7.20 4.86 2.05 7.08 4.80 2.11 6.86 4.72 2.22 6.54 4.59 2.38
19 27 8.01 5.40 1.72 7.69 5.26 1.89 7.36 5.13 2.05 7.23 5.07 2.11 7.03 4.99 2.22 6.71 4.88 2.40
22 30 8.50 5.20 1.74 8.18 5.08 1.91 7.85 4.96 2.07 7.72 4.93 2.13 7.52 4.84 2.24 7.20 4.73 2.40
Remark:
AFR: Air ow rate (m
3
/min)
BF : Bypass factor.
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Capacity (kW)
SHC: Sensible Heat Capacity (kW)
PI: Power Input (kW)
Notes:
1. shows nominal (rated) capacities and power input.
2. TC,PI and SHC must be calculated by interpolation using the gures in the above tables.
3. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5m
Level difference : 0.0m