Electric Characteristic
67
Electric Characteristic
Unit Combination Power Supply COMP OFM IFM
Indoor Unit Outdoor Unit Hz Volts Voltage Range MCA MFA LRA RLA kW FLA kW FLA
FTV28A RV28A
50 220
Max. 50Hz 264V
Min. 50Hz 198V
4.70 16.0 16.0 3.34 0.050 0.22 0.037 0.20
50 230
50 240
FTV35A RV35A
50 220
Max. 50Hz 264V
Min. 50Hz 198V
5.96 16.0 30.1 4.34 0.051 0.23 0.042 0.2050 230
50 240
FTV50A RV50A
50 220
Max. 50Hz 264V
Min. 50Hz 198V
9.19 20.0 38.0 6.74 0.092 0.41 0.044 0.20
50 230
50 240
FTV60A RV60A
50 220
Max. 50Hz 264V
Min. 50Hz 198V
12.4 20.0 52.0 9.11 0.092 0.41 0.077 0.36
50 230
50 240
Symbols:
MCA : Min. circuit amps (A)
MFA : Max. fuse amps (A)
LRA : Locked Rotor Ampere (A)
RLA : Rated loads amps (A)
OFM : Outdoor fan motor
IFM : Indoor fan motor
W : Fan motor rated output (W)
FLA : Full load amps (A)
Notes:
1. RLA is based on the following conditions.
Indoor temp. 27°CDB / 19°CWB.
Outdoor temp. 35°CDB.
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. Be sure to install an earth leak detector.
(This unit uses an inverter, which means that an earth leak
detector capable of handling high harmonics must be used in
order to prevent malfuctioning of the earth leak detector.)