Installation Guideline
Outdoor Installation Guideline
Wall facing one side
Walls facing two sides
Walls facing three sides
More than 50 More than 100
1200 or
less
Side view
More than 50
More than 150
Top view
More than 300
More than
100
More than 50
Top view
More than 50
More than 150
Wall facing one side
Side view
More than 100 More than 350
1200 or
less
Walls facing two sides
Walls facing three sides
Top view
More than
100
More than 50More than 50
More than 350
Top view
More than 50
More than 100
More than 350
(Unit: mm)
Special Precautions When Dealing With R32 Unit
*
Calculation based on Installation Height of 1.8m
*
Max. Allowable Length (L),m for:-
FTV28/35-RV28/35 : 25
FTV50/60-RV50/60 : 30
FTV85PS-RC85A : 50
1. Installing Outdoor Unit
Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation
guidelines below.
For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
Installation of pipe work shall be kept to a minimum and pipe work shall be protected from physical damage and
shall not be installed in an unventilated space;
Reusable mechanical connectors and flare joints shall be accessible for maintenance purposes;
RV28/35 RV50/60, RC85
Model
R32 charge, kg for 7.5m
piping
Minimum floor area, Xm
2
(based on 7.5m piping)
R32 charge, kg for max
allowable pipe length
*
Minimum floor area, Xm
2
(based on max allowable
pipe length
* )
FTV28A - RV28A
0.50 0.24 0.71 0.48
0.68 0.44 0.98 0.91
1.10 1.15 1.48 2.10
FTV35A - RV35A
FTV50A - RV50A
FTV60A - RV60A
1.10 1.15 1.48 2.10
Model
R32 charge, kg for 7.5m
piping
Minimum floor area, Xm
2
(based on 7.5m piping)
R32 charge, kg for max
allowable pipe length
*
Minimum floor area, Xm
2
(based on max allowable
pipe length
* )
FTV28P - RV28F
0.55 0.29 0.85 0.68
0.76 0.55 1.06 1.07
0.75 0.54 1.13 1.22
FTV35P - RV35F
FTV50P - RV50C
FTV60P - RV60C
0.70 0.47 1.08 1.12
Model
R32 charge, kg for 7.5m
piping
Minimum floor area, Xm
2
(based on 7.5m piping)
R32 charge, kg for max
allowable pipe length
*
Minimum floor area, Xm
2
(based on max allowable
pipe length
* )
FTV85PS - RC85A
1.6 2.44 3.30 10.38