2 | Components
Service manual
48
FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05
INFORMATION
The compressor dampers may look different.
Compressor dampers are in a good
condition?
Action
Yes Perform an electrical check of the
compressor, see "2.2.1Checking
procedures"[446].
No Replace the compressor and/or
damaged dampers, see "2.2.2Repair
procedures"[452].
To perform an electrical check of the compressor
1 First perform a mechanical check of the compressor, see "2.2.1 Checking
procedures"[446].
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10VDC before proceeding.
2 Remove the cover of the compressor wire terminals.
a
a Compressor wire terminals cover
3 Disconnect the Faston connectors from the compressor wire terminals U, V
and W.
INFORMATION
Note the position of the Faston connectors on the compressor wire terminals to
allow correct connection during installation.