2 | Components
Service manual
49
FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05
V U
W
U Wire terminal U
V Wire terminal V
W Wire terminal W
CAUTION
Before measuring the compressor motor windings resistance, measure the
resistance of the multimeter probes by holding the probes against each other. If the
measured resistance is NOT 0Ώ, this value MUST be substracted from the measured
winding resistance.
4 Measure the resistance between the compressor motor windings U-V, V-W
and U-W.
Result: All measurements MUST be approximately the same.
Compressor motor winding
measurements are correct?
Action
Yes Continue with the next step.
No Replace the compressor, see
"2.2.2Repair procedures"[452].
5 Measure the continuity of the U, V and W wires between the compressor and
the PCB. If no continuity, correct as needed, see "5.2Wiring diagram"[4171].
6 Connect the Faston connectors to the compressor wire terminals U, V and W