EDUS39-600-F6 Installation
FXAQ-M 31
6. DRAIN PIPING WORK
(1) Install the drain piping. (Refer to Fig. 16)
The drain pipe should be short with a downward slope and should prevent air pockets from forming.
Pay close attention to the directions in Figure 16 when performing drain work.
When extending the drain hose, use a commercially available drain extension hose, and be sure to
insulate the extended section of the drain hose which is indoors. (Refer to Fig. 17)
Make sure the diameter of the extension drain piping is the same as the indoor unit drain hose (hard vinyl chloride,
I.D. 9/16”) or bigger.
In case of converging multiple drain pipes, install them while referring to Fig. 18.
Select diameter of drain piping that adapts to the capacity of the unit connected..
(2) Make sure the drain works properly.
After drain work is complete, perform a
drain check by opening the front panel,
removing the air filter, pouring water
into the drain pan, and making sure water
flows smoothly out of the drain hose.
(Refer to Fig. 19)
Fig. 16
Make sure the drain
hose is at a downward
slope.
Make sure the tip does
not go underwater even
when water is added.
Drain hose
Drain hose
(Downward
slope)
Indoor unit drain hose
Extension drain piping
(commercially available)
Insulating tube
(commercially available)
Insulating tape (accessory) (4)
( See “4.INDOOR UNIT INSTALLATION” )
Fig. 17
Fig. 18
(Slope of at least 1/100)
4 or more
Plastic container
for pouring
Drain pan
Make sure not to splash the water.
Fig. 19