Installation EDUS39-600-F6
32 FXAQ-M
CAUTION
When connecting drain piping, do not connect the drain piping directly to sewage pipes that smell of ammonia. The
ammonia in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger.
Keep in mind that if water collects on the drain pipe it will become blocked.
7. ELECTRIC WIRING WORK
7-1 GENERAL INSTRUCTIONS
All field supplied parts and materials and electric works must conform to local codes.
Use copper wire only.
For electrical wiring work, refer to the WIRING DIAGRAM attached to the unit.
For remote controller wiring details, refer to the installation manual attached to the remote controller.
All wiring must be performed by an authorized electrician.
This system consists of multiple indoor units. Mark each indoor unit as unit A, unit B, and so forth, and be sure the
terminal block wiring to the outdoor unit and BS unit is properly matched. If controls wiring and piping between the
outdoor and indoor units are mismatched, a communications malfunction is likely.
A circuit breaker capable of shutting down power supply to the entire system must be installed.
Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected to the
outdoor unit, the capacity of the circuit breaker and switch, and wiring instructions.
Be sure to ground the air conditioner.
DANGER
Do not ground units to water pipes, telephone wires or lightning rods because incomplete grounding could cause a
severe shock hazard resulting in severe injury or death, and to gas pipes because a gas leak could result in an
explosion which could lead to severe injury or death.
7-2 ELECTRICAL CHARACTERISTICS
MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A)
W: Fan Motor Rated Output (W); FLA: Full Load Amps (A)
7-3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE
Allowable length of transmission wiring and remote controller wiring are as follows.
(1) Outdoor unit - Indoor unit:Max. 3280 ft. (1000 m) Total wiring length: 6560 ft. (2000 m)
(2) Indoor unit - Remote controller:Max.1640 ft. (500 m)
Insulated thickness: 1/16” (1.6 mm) or more.
Units Power supply Fan motor
Model Hz Volts Voltage range MCA MFA W FLA
FXAQ07MVJU
60 208-230
Max. 253
Min. 187
0.3 15 40 0.2
FXAQ09MVJU 0.3 15 40 0.2
FXAQ12MVJU 0.4 15 40 0.3
FXAQ18MVJU 0.4 15 43 0.3
FXAQ24MVJU 0.6 15 43 0.5
Model
Power supply wiring
Remote controller wiring
Transmission wiring
Field fuses Size Wire Size
FXAQ07MVJU
15A
Size must
comply with local
codes.
2 conductor, stranded
copper, non-shielded, PVC
or vinyl jacket
AWG18
FXAQ09MVJU
FXAQ12MVJU
FXAQ18MVJU
FXAQ24MVJU