•VRV
®
Systems • Indoor Units
3
Indoor Units • WALL MOUNTED UNIT • FXAQ-MAVE
1 Specifications
21
1-2 ELECTRICAL SPECIFICATIONS FXAQ20MAVE FXAQ25MAVE FXAQ32MAVE FXAQ40MAVE FXAQ50MAVE FXAQ63MAVE
Power Supply Name VE
Phase 111111
Frequency Hz 50 50 50 50 50 50
Voltage V 220-240
Current Minimum circuit amps
(MCA)
A 0.30 0.40 0.40 0.40 0.40 0.60
Maximum fuse amps (MFA) A 15.00 15.00 15.00 15.00 15.00 15.00
Full load amps (FLA) A 0.20 0.30 0.30 0.30 0.30 0.50
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below
or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA<= 4 x FLA
next lower standard fuse rating minimum 15A
select wire size based on the MCA
instead of a fuse, use a circuit breaker
For more details concerning conditional connections, see http://extranet.daikineurope.com, select "E-Data Books”.
Finally, click on the document title of your choice.