• Indoor Unit • Wall mounted unit • FXAQ-P
1
6
• VRV Systems • Indoor Unit14
6 Capacity tables
6 - 3 Capacity Correction Factor
FXAQ-P
3D079901
Capacity correction factor Te = 11°C
Indoor air
temperature
14.0 °CWB 16.0 °CWB 18.0 °CWB 19.0 °CWB 20.0 °CWB 22.0 °CWB 24.0 °CWB
20.0 °CDB 23.0 °CDB 26.0 °CDB 27.0 °CDB 28.0 °CDB 30.0 °CDB 32.0 °CDB
FXAQ20P
TC 0.549 0.568 0.571 0.604 0.631 0.684 0.723
SHF 1.132 1.231 1.311 1.250 1.203 1.133 1.093
FXAQ25P
TC 0.552 0.572 0.570 0.602 0.629 0.684 0.723
SHF 1.123 1.221 1.312 1.251 1.205 1.132 1.093
FXAQ32P
TC 0.559 0.578 0.573 0.600 0.628 0.685 0.724
SHF 1.107 1.203 1.297 1.250 1.203 1.129 1.095
FXAQ40P
TC 0.547 0.556 0.571 0.611 0.645 0.700 0.746
SHF 1.142 1.245 1.298 1.231 1.181 1.120 1.081
FXAQ50P
TC 0.552 0.565 0.577 0.616 0.651 0.709 0.750
SHF 1.119 1.214 1.282 1.220 1.173 1.113 1.095
FXAQ63P
TC 0.553 0.573 0.580 0.621 0.659 0.717 0.750
SHF 1.102 1.195 1.277 1.217 1.169 1.110 1.093