• VRV Systems • Indoor Unit 13
• Indoor Unit • Wall mounted unit • FXAQ-P
6 Capacity tables
6 - 3 Capacity Correction Factor
FXAQ-P
3D079901
Capacity correction factor Te = 9°C
Indoor air
temperature
14.0 °CWB 16.0 °CWB 18.0 °CWB 19.0 °CWB 20.0 °CWB 22.0 °CWB 24.0 °CWB
20.0 °CDB 23.0 °CDB 26.0 °CDB 27.0 °CDB 28.0 °CDB 30.0 °CDB 32.0 °CDB
FXAQ20P
TC 0.687 0.692 0.742 0.759 0.780 0.813 0.836
SHF 1.132 1.194 1.139 1.116 1.093 1.061 1.046
FXAQ25P
TC 0.691 0.692 0.739 0.759 0.780 0.814 0.836
SHF 1.123 1.193 1.140 1.115 1.093 1.061 1.046
FXAQ32P
TC 0.700 0.692 0.736 0.760 0.781 0.815 0.836
SHF 1.107 1.190 1.140 1.089 1.091 1.059 1.050
FXAQ40P
TC 0.681 0.684 0.748 0.772 0.792 0.824 0.853
SHF 1.142 1.192 1.127 1.101 1.081 1.058 1.037
FXAQ50P
TC 0.688 0.690 0.751 0.775 0.797 0.832 0.854
SHF 1.119 1.182 1.122 1.097 1.077 1.053 1.052
FXAQ63P
TC 0.694 0.690 0.753 0.781 0.806 0.833 0.853
SHF 1.102 1.181 1.121 1.095 1.074 1.054 1.050