•VRV
®
Systems • Indoor Units
3
• Indoor Units • Wall Mounted Unit • FXAQ-MAVE9
1 Specifications
3
1
1-2 ELECTRICAL SPECIFICATIONS (50HZ) FXAQ20MAVE9 FXAQ25MAVE9 FXAQ32MAVE9 FXAQ40MAVE9 FXAQ50MAVE9 FXAQ63MAVE9
Power Supply Name VE
Phase 1~
Frequency Hz 50
Voltage V 220-240
Current Minimum circuit amps (MCA) A 0.3 0.4 0.4 0.4 0.4 0.6
Maximum fuse amps (MFA) A 15
Full load amps (FLA) A 0.2 0.3 0.3 0.3 0.3 0.5
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-3 ELECTRICAL SPECIFICATIONS (60HZ) FXAQ20MAVE9 FXAQ25MAVE9 FXAQ32MAVE9 FXAQ40MAVE9 FXAQ50MAVE9 FXAQ63MAVE9
Power Supply Name VE
Phase 1~
Frequency Hz 60
Voltage V 220
Current Minimum circuit amps (MCA) A 0.3 0.3 0.4 0.4 0.4 0.6
Maximum fuse amps (MFA) A 15
Full load amps (FLA) A 0.2 0.2 0.3 0.3 0.3 0.5
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker