Control Devices EDUS391000-C
40 Controls
2.5 DCS301C71 Unified ON/OFF Controller
Turns up to 16 groups of indoor units (max. 128 units) on/off (operation/stop) by individual group or all at once, and lets
you check display of operation/malfunction at the same time.
2.5.1 System Configuration
This unified ON/OFF controller enables individual and unified operation/stop for a maximum of 16 groups of indoor units.
With 2 to 8 unified ON/OFF controllers, individual and unified control is possible with up to a maximum 128 groups of
indoor units.
The Unified ON/OFF Controller cannot be used in conjunction with the optional Group Control Adapter.
For a maximum of 16 groups of indoor units (max. 128 units),
unified operation/stop or individual operation/stop can be performed
with this optional accessory. Also allows you check operation/error
display at a glance.
By combining with a central remote controller and schedule timer,
you can construct a system that matches the size and use of the
building.
Up to 8 units connectable within 1 system.
Up to 16 units in the double central control mode.
Applicable wiring methods include bus and star in addition to
crossover type.
Can be used in combination with other D-BACS equipment.
When using 1 unified ON/OFF
controller
When using 2 to 8 unified ON/OFF
controllers