2 Specific installer safety
instructions
Always observe the following safety instructions and regulations.
General
WARNING
Make sure installation, servicing, maintenance, repair and
applied materials follow the instructions from Daikin
(including all documents listed in “Documentation set”)
and, in addition, comply with applicable legislation and are
performed by qualified persons only. In Europe and areas
where IEC standards apply, EN/IEC 60335-2-40 is the
applicable standard.
Unit installation (see "12Unit installation"[412])
CAUTION
Appliance NOT accessible to the general public, install it in
a secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for
installation in a commercial and light industrial
environment.
Refrigerant piping installation (see "13Piping
installation"[415])
CAUTION
Piping MUST be installed according to instructions given in
"13Piping installation"[4 15]. Only mechanical joints (e.g.
braze+flare connections) that are compliant with the latest
version of ISO14903 can be used.
CAUTION
Install the refrigerant piping or components in a position
where they are unlikely to be exposed to any substance
which may corrode components containing refrigerant,
unless the components are constructed of materials that
are inherently resistant to corrosion or are suitably
protected against corrosion.
Electrical installation (see "14Electrical installation"[416])
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
▪ All wiring MUST be performed by an authorised
electrician and MUST comply with the applicable
national wiring regulation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical
construction MUST comply with the applicable
legislation.
WARNING
▪ If the power supply has a missing or wrong N-phase,
equipment might break down.
▪ Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth.
Incomplete earthing may cause electrical shocks.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or
piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, extension cords, or
connections from a star system. They can cause
overheating, electrical shocks or fire.
▪ Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase
advancing capacitor will reduce performance and may
cause accidents.
WARNING
Use an all-pole disconnection type breaker with at least
3 mm between the contact point gaps that provides full
disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
Commisioning (see "15Commissioning"[418])
WARNING
If the panels on the indoor units are not installed yet, make
sure to power OFF the system after finishing the test run.
To do so, turn OFF operation via the user interface. Do
NOT stop operation by turning OFF the circuit breakers.
For the user
3 User safety instructions
Always observe the following safety instructions and regulations.
3.1 General
WARNING
If you are NOT sure how to operate the
unit, contact your installer.
WARNING
This appliance can be used by children
aged from 8 years and above and
persons with reduced physical, sensory
or mental capabilities or lack of
experience and knowledge if they have
been given supervision or instruction