Daikin FXFQ63P9VEB - Dimensional Drawing with Accessories

Daikin FXFQ63P9VEB
37 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
•VRV
®
Systems • Indoor Units
16
Indoor Units • Round Flow Cassette • FXFQ-P9VEB
5 Dimensional drawing & centre of gravity
5 - 3 Dimensional drawing with accessories
FXFQ20,25,32,40,50,63P9
3D057035
Nr Name Description
1 Indoor unit
2 Decoration panel
3 Suction chamber
4 Connecting chamber (Right)
5 Connecting chamber (Left)
Service acces panel:
450x450 mm or more
NOTES
1 When installing this kit, inspection hatch is necessary.
(It is necessary when servicing.) Either one of
inspection hatches must be installed.
2 Field construction.
3 The corner air outlet of this part must be shut.
4 In case of mounting a duct fan, make sure to
use a wiring adapter for electrical appendices
and link with the indoor unit fan.
5 The intake air flow rate is recommended to be 20%
or less of the H speed air flow rate.
If the intake air flow rate is too large, the operating
sound may rise or detection of the indoor unit suction
temperature may be affected.
6 It indicates the distance between the T-tube inlet and the
indoor unit inlet when the T-tube is connected.
(Refer to note: 1)
Service acces panel:
450 x 450 mm or more
(Refer to note: 1)
Installation service access panel
Pipe connection side
Drain connection side
Note: 3
Note: 3
Inlet
T-tube
Field supply
Air flow rate (m
3
/min)
Ventilation resistance in chamber (Note: 6)
Static pressure of chamber (Pa)
Connecting chamber mounting space
455 (Ceiling opening space)
view
(1000)
FXFQ80,100P9
3D057034
Nr Name Description
1 Indoor unit
2 Decoration panel
3 Suction chamber
4 Connecting chamber (Right)
5 Connecting chamber (Left)
Service acces panel:
450x450 mm or more
NOTES
1 When installing this kit, inspection hatch is necessary.
(It is necessary when servicing.) Either one of
inspection hatchs must be installed.
2 Field construction.
3 The corner air outlet of this part must be shut.
4 In case of mounting a duct fan, make sure to
use a wiring adapter for electrical appendices
and link with the indoor unit fan.
5 The intake air flow rate is recommended to be 20%
or less of the H speed air flow rate.
If the intake air flow rate is too large, the operating
sound may rise or detection of the indoor unit suction
temperature may be affected.
6 It indicates the distance between the T-tube inlet and the
indoor unit inlet when the T-tube is connected.
(Refer to note: 1)
Service acces panel:
450 x 450 mm or more
(Refer to note: 1)
Installation service access panel
Pipe connection side
Drain connection side
Note: 3
Note: 3
Inlet
T-tube
Field supply
Air flow rate (m
3
/min)
Ventilation resistance in chamber (Note: 6)
Static pressure of chamber (Pa)
Connecting chamber mounting space
455 (Ceiling opening space)