1 Specifications
Decoration Panel 2 Model BYCQ140CW1W
Colour White (RAL9010)
Dimensions Height mm 50
Width mm 950
Depth mm 950
Weight kg 5.5
Decoration Panel 3 Model BYCQ140CGW1
Colour White (RAL9010)
Dimensions Height mm 130
Width mm 950
Depth mm 950
Weight kg 5.5
Air Filter Resin net with mold resistance
Standard Accessories Operation manual
Installation manual
Drain hose
Clamp for drain hose
Washer for hanger bracket
Screws
Installation guide
Insulation for fitting
Sealing pads
Drain sealing pad
Notes Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level
difference: 0m
Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level
difference: 0m
The sound pressure values are mentioned for a unit installed with rear suction
The sound power level is an absolute value indicating the power which a sound source generates
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat
The BYCQ140CW1W has white insulations. Be informed that formation of dirt on white insulations is
more visible and that it is consequently not advised to install the BYCQ140W1W decoration panel in
environments exposed to concentrations of dirt
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is
not below or above listed range limits
Maximum allowable voltage range variation between phases is 2%
MCA/MFA: MCA = 1.25 x FLA
MFA 4 x FLA
Next lower standard fuse rating minimum 16A
Select wire size based on the value of MCA
Instead of a fuse, use a circuit breaker
Power supply Name VE
Phase 1~
Frequency Hz 50/60
Voltage V 220-240/220
Voltage range Min. -10
Max. 10
Current - 50Hz Minimum circuit amps (MCA) A 0.4 0.5 0.6
Maximum fuse amps (MFA) A 16
Full load amps (FLA) A 0.3 0.4 0.5
Current - 60Hz Minimum circuit amps (MCA) A 0.4 0.5 0.6
Maximum fuse amps (MFA) A 16
Full load amps (FLA) A 0.3 0.4 0.5
1-1 Technical Specifications FXFQ20P9VEB FXFQ25P9VEB FXFQ32P9VEB FXFQ40P9VEB FXFQ50P9VEB