Capacity Tables EDUS39-900-F10
10 FXMQ-MF
FXMQ72MFVJU
Cooling
Heating
Notes
:
1. The above capacities are based on the following conditions:
Air discharge temperature setting: 64°F for cooling operation,
77°F for heating (Factory setting).
Equivalent piping length: 25ft.
Level difference: 0ft.
2. The above capacities values are general average values which can be generated by each compressor operation level.
3. A value enclosed in means rated capacity.
Outdoor air temp FWB
FDB
62 66 70 74 78 82 86 90
capacity
Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h
67 19600 24000 - - - - - -
71 19600 24000 27600 - - - - -
75 19600 24000 27600 34700 - - - -
79 - 24000 27300 34400 - - - -
83 - - 27300 34000 56500 - - -
87 - - 27000 33700 55900 72600 - -
91 - - 27000 33100 55600 72000 84200 -
95 - - - 32700 54900 71300 83800 89300
Outdoor air temp FWB
FDB
19 23 27 31 35 39 43 51 55
capacity
Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h
22 50700 50700 - - - - - - -
32 - - 47000 - - - - - -
37 - - 41200 41200 41200 - - - -
42 - - - - 33800 33800 33800 - -
52 - - - - - 26300 26300 26300 -
57 - - - - - - 18900 18900 18900