EDUS39-900-F10 Capacity Tables
FXMQ-MF 9
6. Capacity Tables
FXMQ48MFVJU
Cooling
Heating
Notes
:
1. The above capacities are based on the following conditions:
Air discharge temperature setting: 64°F for cooling operation,
77°F for heating (Factory setting).
Equivalent piping length: 25ft.
Level difference: 0ft.
2. The above capacities values are general average values which can be generated by each compressor operation level.
3. A value enclosed in means rated capacity.
Outdoor air temp FWB
FDB
62 66 70 74 78 82 86 90
capacity
Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h
67 13000 15900
71 13000 15900 18300
75 13000 15900 18300 23300
79 15900 18300 22900
83 18300 22900 37700
87 17900 22600 37300 48300
91 17900 22200 37000 48000 56200
95 21900 36600 47600 55800 59600
Outdoor air temp FWB
FDB
19 23 27 31 35 39 43 51 55
capacity
Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h
22 32600 32600 - - - - - - -
32 - - 30000 - - - - - -
37 - - 26600 26600 26600 - - - -
42 - - - - 21500 21500 21500 - -
52 - - - - - 16800 16800 16800 -
57 - - - - - - 12100 12100 12100