ESIE15-11A | Part 3. Field settings 2. Wired remote controller BRC2/3E52
Page 26 23/09/16
VRV4 indoor units
1c 0 display of actual room temperature 01 off
02
on
1 selection air thermistor shown in room
temp display
01 air return (R1T) For auto-function & setback
02
thermistor of BRC1E
2 Selection mode display in auto mode 01 off Whether or not 'heating/cooling’ is dis-
played during automatic mode (other-
wise only 'automatic' is mentioned on
remocon)
02
on
4 backlight on 01 permanently off
02
on for 30 seconds when
pushing any button
Backlight goes off again after 20 sec-
onds
03 always on
6 display of remocon 01
permanent display the screen always shows values
02 screen goes blank after 5
minutes
touching any button will reactivate the
screen
12 External input BC-B1 (window con-
tact) of pcb board BRP7A51
01
don't use
02 use
13 External input BC-B2 (keycard con-
tact) of pcb board BRP7A51
01
don't use
02 use
1e 1 enable temperature display in °C or °F 01
not visible from factory locked to °C
02 visible visible in menu, choice between °C
and °F
2 "setback" - function 01 not available Setback is home leave function
02 available for heating
03 available for cooling
04
available for heating &
cooling
5 hour indication 01
not visible in menu default 24h is activated
02 visible in menu enduser can choose 24h or 12h dis-
play
6 count down timer 01 not visible in menu
02
visible in menu